Hall Effect Sensor SC172T
video

Hall Effect Sensor SC172T

SC172T series are closed loop hall effect current transducers, With galvanic isolation between primary and secondary circuit, mainly applied in the DC, Ac and pulse current.
Send Inquiry
Product Introduction

Electrical data(Ta=25℃±5)

Part No
Specific.

SC172T-2000A/ 400mA

Unit

Nominal primary current(Ipn)

±2000

A

Peak current(Ipm)

0..±3000

A

Nominal output (Iout)

±400

mA

Load resistor(RL)

@ Vc=±15V, ±2000A RL≤1

@ Vc=±24V, ±2000A RL≤20

@ Vc=±24V, ±3000A RL≤9

Ω

Power supply(Vc)

±15~±24

V

Current consumption(Ic)

@ Vc=±15V ,Ip=0 ≤30

mA

Accuracy(X)

@ Vc=±15~±24 ≤±0.5

%FS

Linearity (ε)

@Ip=0-±Ipn ≤0.1

%FS

Electrical offset error (Ioe)

@Ip=0 ,TA=25℃ ≤±0.2

mA

Magnetic offset error (Ioh)

@Ip=±Ipn-0 ≤±0.2

mA

Thermal drift (TCIoe)

@ -40~+85℃, ≤±0.2

mA

Response time(tr)

@50A/μS, 10%-90% ≤3

μS

Band width (BW)

@ -3dB 0~100

KHz

Operating temperature(TA)

-40~+85

Storage temperature(TS)

-50~+90

Mass(m)

1376

g

Isolation voltage(Vd)

@ 50HZ,AC,1min 3.0

KV

Isolation resistor(Ris)

200

Creepage distance(dCp)

6.4

mm

Space distance(dCi)

6.4

mm

 

APPLICATION

  • AC variable speed and servo motor driver
  • DC motor drive static converter
  • Frequency converter
  • Welding machine
  • Telecommunication power supply
  • UPS
  • Switch power supply

 

DIMENSION(MM)

product-728-494

General tolerance:±0.5mm。

 

STANDARD FOLLOWED

  • UL94-V0
  • EN60947-1:2004
  • IEC60950-1:2001
  • EN50178:1998
  • SJ 20790-2000

Hot Tags: hall effect sensor sc172t, China hall effect sensor sc172t manufacturers, suppliers, factory, Current And Voltage Transducer, Closed Loop Hall Effect SC1BT, Closed Loop Hall Effect Current Sensor, Hall Effect Current Transducer SC135T, Hall Effect Sensor SC172T, Current Sensor SLD1 P